mini is more. puls gmbh, arabellastrasse 15, 81925 munich tel. +49.(0)89.9278-244, fax: +49.(0)89.9278-299 sales@puls-power.com, http://www.puls-power.com puls does it again: practical, versatile and reliable like the silverline ? yet small like no other. miniline ml100.100 mounted and connected in record time, no tools required world-wide approvals (ul, en, csa, cb scheme) for industry and office/ home tiny: wxhxd = 73 x 75 x 103mm hazardous location class i div. 2 (ul 1604) adjustable output voltage up to dc 28v 115/230v auto select input puls overload design? (high output overload capability) selectable single/parallel operation (jumper) with dc 24-28v / 100w ml100e100/040629 data sheet
x input input voltage ac 100-120/220-240v (auto select), 47...63 hz (ac 85...132v / ac 184...264v, dc 220...375v n= + and l= - ) input current <2.1a (@ ac 100v in , 100w p out ) <1a (@ ac 220v in , 100w p out ) external fusing not required, un it provides internal fuse (t3a15h, not accessible) transient immunity transient resi stance acc. to vde 0160 / w2 (750v/ 1.3 ms), over entire load range hold-up time (see diagram below) >40 ms @ ac 230v, 24.5v / 4.2a >20 ms @ ac 196v, 24.5v / 4.2a >20 ms @ ac 100v, 24.5v / 4.2a x efficiency, reliability efficiency losses typ. 90% (ac 230v, 24.5v / 4.2a) (see also diagram below) typ. 11.4w (ac 230v, 24.5v / 4.2a) mtbf (reliability) appr. 500.000 h acc. to siemensnorm sn 29500 (24.5v / 4.2a, ac 230v, t amb = +40 c) prior to shipment, every unit undergoes the following tests in order to isolate any defective units which might suffer an early failure: run-in / burn-in (full load, t amb = +60c, on/off cycle) functional test (100 %) x construction, mechanics, installation robust plastic housing (us patent no. d442, 923s), fine ventilation grid on three housing sides to keep out small parts (e.g. screws), ip20 dimensions and weight w x h x d weight 73 mm x 75 mm x 103 mm (+ din rail) depth incl. terminals: 98 mm (+ din rail) 360 g mounting orientation , or (cf. ?output?) ventilation/cooling free space f. cooling normal convection, no fan required recom'd.: 25 mm on sides with ventilation grid easy snap-on mounting onto the din-rail (ts35/7,5 or ts35/15). unit sits safely and firmly on the rail; no tools required even to remove connection by spring clamp terminals; uniformly firm hold, vibration-resistant and maintenance-free: 2 terminals per output connector size range flexible cable solid cable wire strip length 0.3-2.5mm 2 (28-12 awg) 0.3-4mm 2 (28-12 awg) ferrules admissible 6mm (0.24in) recommended design details ? for your advantage: all terminals are easy to reach as mounted on the front panel. input and output are strictly apart from each other (input below, out- put above) and so cannot be mixed up. ? mounting and connection do not require any screwdriver easy, quick, durable and reliable installation. x diagrams 0 5 10 15 20 25 30 35 012345678 output current iout [a] output voltage vout [v] vin = ac 115/230v 'single use' vin = ac 115/230v 'parallel use' 0 20 40 60 80 100 120 -10 0 10 20 30 40 50 60 70 ambient temperature [c] output power [w] 0 20 40 60 80 100 120 140 160 80 120 160 200 240 280 input voltage vacin [v] hold-up time [ms] pout=100w, typ. pout=100w, min. pout=50w, typ. pout=50w, min. 83 84 85 86 87 88 89 90 91 11,41,82,22,633,43,84,2 output current iout [a] efficiency [%] 1 1 5 v ac i n 2 3 0 v ac i n output characteristic v out /i out (min.) efficiency hold-up time with acin (@ v out = 24.5v, typ.) (at v out = 24.5v, typ. + min.) derating of output power mounting 85-132 v acin a-a a-b a-b 185-264 v acin a-a a-b a-b 220-375 v dcin a-a a-b a-b a b a x output output voltage preset dc 24-28v (adj. by front panel potentiometer) 24.5v 0.5% @ 4.2a voltage regulation stat. <1% v out (jumper in pos. 'single use') stat. <3% v out (jumper in pos. 'parallel use'), dyn. 1.5% v out over all ripple/noise <50mv pp (20 mhz bandw., 50 ? measurem.) overvoltage prot. (ovp) <36v output noise suppression emi values below en 61000-6-3, even when using long (>2m), unscreened output cables rated continuous loading up to 4.2a @ 24.5v / 3.6a @ 28v (convection cool- ing), depending on built-in orientation, v in and t amb for details see derating diagram below overload behaviour puls overload design?: no switch-off at overload/short-circuit, instead: up to 1.9 ? i rated. so you need no oversi zing to start awkward loads. protection unit is protected against (also permanent) short- circuit, overload and open-circuit. derating depending on built-in orientation; see diagram below parallel operation yes (selectable by front panel jumper) power back immunity 35v operating indicator green led x environmental data, emc, safety ambient temperature range (measured 25 mm below unit) storage/transport operation -25c ... +85c -10c ... +70c (for dera ting see diagram below) humidity max. 95% (without condensation) electromagnetic emissions (eme) en 61000-6-3 (includes en 61000-6-4) class b (en 55011, en 55022) incl. output noise suppression en 61000-3-2 (pfc) electromagnetic immunity (emi) en 61000-6-2 (includes en 61000-6-1) safe low voltage: prot. class/degree: selv (en 60950, vde0100/t.410), pelv (en 50178) class 1 (en 60950) / ip20 (en 60529) the psu complies with all major safety approvals for eu (en 60 950, en 60204-1, en 50178), usa (ul 60950, e137006, ul508 listed, e198865), canada (can/csa-c22.2 no 60950 [cur], can/csa-c22.2 no. 14 [cul]), cb scheme (iec 60950). hazardous location class i div. 2 (ul 1604) technical data ml100 .100 product information (ml100e100), rev.: 29. june 2004. unless othe rwise stated, specifications ar e valid for ac 230v input volta ge, +25c ambient temperature, and 5 min. run-in time. they are subject to change without prior notice. puls gmbh, arabellastra?e 15, d-81925 mnchen x tel: +49.(0)89.9278-244, fax: +49.(0)89.9278-299, e-mail: sales@puls-power.com x www.puls-power.com s p r i n g c l a m p s
|