re v date change detail general cable 20 forge park, franklin, ma 02038 phone: 508-541-7100 fax: 508-541-8122 title: C8102 description: 4 c 18 awg plenum cable created by: a 06/29/09 initial release -vm final approval: vm 6/29/09 page 1 of 1 general cable reserves the right to modify this inf ormation without prior notification and does not ma ke a warranty or representation of any kind, whethe r implied or expressed with respect to the informat ion contained herein. general cable assumes no risks, and will n ot be liable for direct or indirect, special; incid ental or consequential damages, any defect or perso nal injury resulting from the use of this document. description: tinned copper conductor, fep insulatio n, conductors cabled and plenum-pvc jacketed plenum cable. a. construction: 1.0 primaries: 1.1 conductor: awg stranding nom. dia 1.2 insulation: material nom. thickness nom. od 18 awg 19/30 tinned copper; .048" fep .007 .062" 1.3 no. of conductors 4 1.4 color code black, white, red, green 3.0 overall cabling: four conductors cabled 4.0 jacket material: plenum pvc nom. wall: .01 4 color: tbd 5.0 overall diameter of cable nom. .178 6.0 marking: surface print: general cable (f) C8102 4c 18 awg cmp (ul) c(ul) - --- rohs aaaaa* * indicates shop order number b. characteristics: 1.0 conductor dc resistance @20c max. (ohm)/1000: 6.2 2.0 capacitance between conductors nom. (pf/ft): 2 1.5 3.0 min. bend radius (inches): 1.8 4.0 max. pulling tension lbs: 90.0 5.0 operating voltage nom.: 300 v 6.0 continuous operating temp: 75c c. approvals: ul Ccmp ; c(ul) cmp
|