  data sheet this instrument converts the optical signal from a mas- ter station or the like into a pneumatic signal (0.2 to 1.0 kgf/cm 2 , etc.) in order to drive a diaphragm type control valve. the operating position of the valve is fed back via link to this positioner to enable accurate positioning. a built-in microcomputer provides intelligent digital pro- cessing of signals with a high precision, and the use of a piezo- electric element flapper makes for a low power consumption. this articles are 6mm optical fiber cable connection type. ambient humidity: 0 to 95%rh transmission: half-duplex bidirectional optical transmis- sion system using single optical fiber cable transmission distance; 1.2km max. (not affected by noise, surge or the like) applicable valve: diaphragm control valve with top diam- eter of 240 or more; stroke 10 to 90mm (feedback lever rotating angle 10 to 30 ) accuracy rating: 1.0% of full scale (output ripple approx. 0.2%) response speed: approx. 4 seconds (for 90% response) (with control valve having top diameter 240 and lift of 16mm) input/output characteristic: linear reference air consumption: 12n r /min (at supply air pressure of 140kpa {1.43kgf/cm 2 } 20n r /min (at supply air pressure of 240kpa {2.45kgf/cm 2 } maximum air supply/discharge flow rate: 60n r /min (at supply air pressure of 140kpa {1.43kgf/cm 2 } 80n r /min (at supply air pressure of 240kpa {2.45kgf/cm 2 } performance specifications functional specifications input signal: ffi system optical digital signal operating air pressure, supply air pressure: power supply: built-in lithium battery (single battery lasts about 2 years) self-diagnosis: diagnosis results can be displayed on op- tional indicator unit and also transmitted to master station. notes: *( 1 ) hhc: hand-held communicator, ms: master station ( 2 ) when output overflows, or offset is large operation at emergency: output operation is settable by remote means (hhc, ms) in an emergency (when input fails) (available on request). holding of output value just before fail- ure ?scale-out of set value below 0% ?scale-out of set value above 100% explosionproofing: jis i3ng5, unnecessary for safety-barrier ambient temperature: ?0 to +60 c (?0 to +60 c for indica- tor unit) storage temperature: ?0 to +70 c operating air pressure 19.6 to 98.1kpa {0.2 to 1.0kgf/cm 2 } 39.2 to 196.1kpa {0.2 to 2.0kgf/cm 2 ) 3 to 15psi 3 to 27psi 6 to 30psi supply air pressure 140kpa {1.43kgf/cm 2 } 240kpa {2.45kgf/cm 2 } 20 1psi 32 1psi 35 1psi contents battery voltage output failure (* 2 ) battery voltage drop hhc, ms (* 1 ) indication zlf ffi system optical-pneumatic positioner specifications date EDS9-50B jul. 31, 1994
zlf structure, materials enclosure structure: jis c0920, splash-proof (equivalent to iec ip54) finish: epoxy/polyurethane double coating, silver (casing cover ..... blue) outer dimensions (h x w x d): 257 x 165 x 220mm mass {weight} approx. 5kg mounting method: on control valve yoke section three sizes, small, medium and large, or links and clamps are available for mounting on valve stem. optical cable and connection method: fuji's designated optical cable (to be pur- chased separately). connection is made by optical connector. air piping connection: rc 1/4 (pt1/4); 1/4?8npt available on request optional specifications indicator unit: indicating section; 4 digit lcd (?0 to +60 c) setting section; 4 pushbutton switches output pressure gauge: jis class 3: 0 to 2 or 0 to 3kgf/cm 2 scale (depends on output range) two built-in lithium batteries: changed over by internal selector switch (standard specification allows accom- modating two batteries) acid/alkali-proof treatment: 304 stainless steel for bolts and washers pneumatic type controlled device o/p positioner sup 8 lines master station optical star coupler fxq system configuration diagram
notes: *( 1 ) positioner operation normal operation: operating air pressure increases with increase of setting single reverse operation: operating air pressure decreases with increase of setting single *( 2 ) valve operation normal operation: valve stem lowers with increase of operating air pressure reverse operation: valve stem rises with increase of operating air pressure code symbols l zf 1- 2 1 345678 10111213 9 description piping connection rc 1/4 (pt1/4) 1/4 18npt indicator unit pressure gauge explosionproofing specification general use (non-explosionproof) intrinsically safe explosionproofing jis i3ng5 no. of built-in lithium batteries one two link mechanism valve operation none with small link mechanism with medium link mechanism with large link mechanism none with small link mechanism with medium link mechanism with large link mechanism treatment for general use acid/alkali-proof treatment operation at emergency holding of output value just before failure scale-out of set value below 0% scale-out of set value above 100% 6 optical cable protection adapter note: for 9mm connector: non-standard item, on request operating air supply air operation pressure pressure 19.6 to 98.1kpa 140kpa {0.2 to 1.0kgf/cm 2 } {1.43kgf/cm 2 } 39.2 to 196.1kpa 240kpa {0.4 to 2.0kgf/cm 2 } {2.45kgf/cm 2 } 3 to 15psi 20psi 6 to 30psi 35psi 3 to 27psi 32psi 98.1 to 19.6kpa 140kpa {1.0 to 0.2kgf/cm 2 } {1.43kgf/cm 2 } 196.1 to 39.2kpa 240kpa {2.0 to 0.4kgf/cm 2 } {2.45kgf/cm 2 } 15 to 3psi 20psi 30 to 6psi 35psi 27 to 3psi 32psi normal operation(* 1 ) b c a b a b c d 1 2 3 4 5 6 7 8 9 a a b c d e f g h a b c y b 1 2 0 1 reverse operation(* 1 ) normal operation(* 2 ) reverse operation(* 2 )
positioner and mounting bracket optical star coupler (data sheet no. eds8-48) hhc (data sheet no. eds 8 44) master station (data sheet no. eds 11 86) optical connector, cable 1. product name 2. type 3. other necessary items 218 115 206 4.5 46 188 10 ? to 30 ? 22 90 136 5 57 12 18 76 88 122 121 76 66 19 6.2 16 l 1 l 2 56 2- 11 mounting holes indicator unit (option) m42 thread 1 depth 4.8 air piping connection 13 output pressure gauge (option) adapter 1/2-14npt (option) valve stem out. sup. positioner with adapter (option) for optical cable protection link mechanism ( b, c, d, f, g, h ) l 1 13 l 2 35 b,f 30 50 c,g 55 112 d,h 55 zlf outline diagrams (unit:mm) ordering information related devices scope of delivery information in this catalog is subject to change without notice. printed in japan head office 6-17, sanbancho, chiyoda-ku, tokyo 102-0075, japan http://www.fesys.co.jp/eng sales div. international sales dept. no.1, fuji-machi, hino-city, tokyo, 191-8502 japan phone: 81-42-585-6201, 6202 fax: 81-42-585-6187 http: //www.fic-net.jp/eng caution on safety *before using this product, be sure to read its instruction manual in advance.


▲Up To Search▲   

 
Price & Availability of EDS9-50B

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X