gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 specifications are for information only, are not intended for installation purposes, and are subject to change without notice. no responsibility is assumed by gamewell-fci for their use. ?2007 honeywell international inc. all rights reserved. www.gamewell-fci.com cs-2044 rev. a page 1 of 2 pid-95, PID-95P point identification device description the gamewell-fci pid-95-p addressable point identifica- tion device is the interface between the non-powered, nor- mally open, dry-contact devices and gamewell-fci?s 600 series of analog addressable fire alarm control panels (facps). point identification devices monitor a single style b circuit, and are designed for concealed mounting in an electrical backbox. the PID-95P can be surface-or-flush mounted and has a visible led for alarm/annunciation. operation the point identification device connects to the signaling line circuit (slc) via two wires. the pid-95 will monitor, via a two-wire supervised slc circuit, contact-type devices such as a waterflow switch or manual station. upon activa- tion of the monitored device, the pid-95 will report its address to the 600 series facp via the analog slc. the control panel will then activate into all alarm programmed outputs related to the pid-95. programming the pid-95 is programmed by setting a single dip switch, easily accessible on the device?s printed circuit board. the dip switch sets the address of the device and the priority interrupt (dip sw #8). all other programming is accom- plished at the facp through a laptop computer or the con- trol panel operator?s display. standard application the pid-95 is the interface between dry-contact type devices and the slc of the control panel. the pid-95 is a means of connecting and identifying monitor points without the use of conventional input modules at the main control panel. the use of pid-95s can dramatically reduce the field wiring required on many projects. features ? monitors dry-contact devices. ? led for alarm annunciation. ? supervises dc power in. ? field programmable. ? priority interrupt. ? plate-mounted version available for surface or flush mounting in 4" (11 cm) square, 4.688" (11.908 cm) , or double gang boxes. microsoft ? windows ? is a registered trademark of microsoft ? corporation. cs-2044ph1.wmf pid-95 PID-95P an iso 9000-2000 company approved fm signaling s521 7300-1288:147 mea approved
gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 cs-2044 rev. a page 2 of 2 www.gamewell-fci.com engineer?s specifications addressable interface devices shall be provided for the monitoring and supervision of contact type devices con- nected to the fire alarm control panel. the devices shall monitor a normally open dry contact. the addressable interface devices shall communicate to the main control panel via the analog addressable circuit. the interface device shall be gamewell-fci pid-95 or PID-95P. specifications pid-95 standby current: 0.0005 a alarm current: 0.0015 a operating temperature: 0 c to 49 c (32f to 120 f) relative humidity: 85%, non-condensing mounting: 4" (10.16 cm) square backbox with blank cover plate PID-95P standby current: 0.0005 a alarm current: 0.0015 a operating temperature: 0 c to 49 c (32f to 120f) relative humidity: 85%, non-condensing mounting: 4" (11 cm) 4.688" (11.908 cm) , double gang backbox. ordering information model description pid-95 addressable point identification device for monitoring contact devices. PID-95P addressable input interface device mounted on 4.688" (11.908 cm) plastic plate. 70839 trim ring for flush-mounting on the PID-95P.
|