Part Number Hot Search : 
00030 FDT434 5962R C6002RU PHFM104 T250010 KSR1107 CSH210R
Product Description
Full Text Search
 

To Download DDI6000 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 DDI6000
Plug-in display for 4...20 mA measuring transmitter
FEATURES * Loop powered * Plug-in directly to transmitter * Loop voltage drop only 3 V at 20mA * Large display range of -1999 to 9999 digits * Scale easily adjustable to transmitter range
The DDI6000 display can be used with all 4...20 mA output devices of the following Sensortechnics transmitter series: KTE/KTU3000 KTE/KTU6000 BTE/PTU6000 BTE/PTU4000
GENERAL DESCRIPTION
The DDI6000 is a microprocessor controlled loop powered display for any 4...20 mA standard signal. It does not require its own separate voltage source as it is supplied directly from the measuring current loop. The measured value is displayed on a 4-digit LCD with a wide max. display range of -1999 to +9999 digits. The operating range of the display device can be directly adjusted to the transmitter without any accessories being required. Simply enter the maximum and minimum measuring range limits and the decimal point position. Parameter and limit values are entered via three keys which are accessible after removal of the cover. All programmable parameters of the DDI6000 are saved in an EEProm. In case of a current failure they will be stored for at least 10 years. The DDI6000 is equipped with a self-diagnosis system to continuously monitor the essential parts of the device for their correct function. An additional monitoring system checks for the sensor for "sensor damage", "sensor short circuit" or values exceeding or falling below permissible limits. Both systems ensure maximum operational reliability of the device. Prior to delivery the DDI6000 will be tested and accurately calibrated. However, prior to starting your installation please configure the device for your application. Please refer to chapter "Configuration".
October 2004 / 627
1/4
www.sensortechnics.com
DDI6000
Plug-in display for 4...20 mA measuring transmitter
TECHNICAL SPECIFICATION
Input signal Max. allowed input current Reverse voltage protection Voltage load Display Display range Maximum display value Minimum display value Decimal point Measuring accuracy Temperature drift Measuring interval Filter Nominal temperature Ambient temperature Relative atmospheric humidity Electromagnetic compatibility additional error: Housing Connection IP rating
4...20 mA (2-wire) 40 mA Polarized plug approx. 3 V 10 mm high LCD-display starting and end value freely selectable 9999 digits -1999 digits any position 0.2 % 1 digit 100 ppm/C approx. 5 measurements / sec. 3 stages can be switched on 25 C 0 to 50 C 0 to 80% (non condensing) In accordance with EN50081-1 and EN50082-2 <1% ABS. Front screen made of polycarbonat 48.5 x 48.5 x 35.5 mm (L x W x D) Specially designed adaptor for cubic plug DIN43650 for simple connection. Front side IP65
October 2004 / 627
2/4
www.sensortechnics.com
DDI6000
Plug-in display for 4...20 mA measuring transmitter
ELECTRICAL CONNECTION
To connect the DDI6000 simply plug into an existing transmitter by means of a special adaptor for the DIN43650 plug. Supply voltage: Device takes power directly from measuring current. Please allow for an additional loop voltage drop of 3 Volts.
Caution!
Wrong electrical connection may lead to the destruction of the device. Mind the maximum input current rating of 40 mA under any circumstances!
FAULT CODES
In case of unacceptable conditions in the system a fault code will be displayed. Fault codes have been defined as follows: FE 1: Measuring range has been exceeded This fault code indicates that the measuring range of the A/D converter has been exceeded. Potential fault cause: Transmitter damaged Short-circuit in transmitter connection DDI6000 not or incorrectly configured FE 1 will be reset as soon as the measuring values return to their permissible range. Please check your transmitter and transmitter connecting cables.
Remedies:
FE 2: Measuring values have fallen below permissible range This fault code indicates that the measuring values of the A/D converter have fallen below the permissible range. Potential fault cause: Transmitter damaged Transmitter connection interrupted DDI6000 not or incorrectly configured FE 2 will be reset as soon as the measuring values return to their permissible range. Please check your transmitter and transmitter connecting cables.
Remedies:
October 2004 / 627
3/4
www.sensortechnics.com
DDI6000
Plug-in display for 4...20 mA measuring transmitter
CONFIGURATION
Please note: Measuring current should be at least 4 mA during configuration! 1. Press button 1, "dP" (decimal point) will be displayed. Select decimal point position desired using buttons 2 and 3. Acknowledge decimal point position by pressing button 1. "dP" will be displayed again. Press button 1 once again, "An4" (display for 4 mA) will be displayed. Use buttons 2 and 3 to set value to be displayed for an input signal of 4 mA. Acknowledge value displayed by pressing button 1. "An4" will be displayed again.
(Buttons 2 and 3 are equipped with a scrolling function, i.e. the value will be increased respectively decreased by 1 digit when pressed briefly (no more than 1 s). When pressing for a longer time (over 1 s) the values start "scrolling" with the speed being increased after approx. 6 s.)
2.
3.
Switch over to the next parameter by pressing button 1 again. "An20" will be displayed (display for 20 mA). Use buttons 2 and 3 to set value to be displayed for an input signal of 20 mA. Acknowledge value displayed by pressing button 1. "An20" will be displayed again. Press button 1 once again. "LI" (limit) will be displayed. Select measuring range limits desired using buttons 2 and 3. 0 = Values exceeding/falling below limits are acceptable. (FE1, FE2 displayed for hardware limits) 1 = Values exceeding/falling below limits are not acceptable. (FE1, FE2 displayed for area limits) Acknowledge selection made by pressing button 1. "LI" will be displayed again. For pressure measuring transducers always enter "LI 0", for relative humidity, pH and similar measuring units always enter "LI 1".
4.
5.
Press button 1 once again. "FILt" (filter) will be displayed. Select input filter 0, 1, 2 or 3 desired using buttons 2 and 3. 0 = no filter 1 = filter 1 active 2 = filter 2 active 3 = filter 1 and 2 active Filter 1: For filtering short pikes occurring when relays and contactors are switched. Make sure to always activate filter 1 if high loads are switched in the vicinity of the DDI6000, wires or the sensor or if large pikes are to be expected. Additional display delay: approx. 0.5 s Filter 2: Prevents "jumping" of the last figure, a phenomenon often found with digital displays and controllers. Make sure to always activate filter 2 if the display range exceeds 2000 digits. Additional display delay: approx. 1 s Acknowledge selection made by pressing button 1. "FILt" will be displayed again.
The adjustment of the DDI6000 to the transmitter is now completed. The DDI6000 can be immediately switched over to display the current measuring value by pressing button 1.
Sensortechnics reserves the right to make changes to any products herein. Sensortechnics does not assume any liability arising out of the application or use of any product or circuit described herein, neither does it convey any license under its patent rights nor the rights of others. October 2004 / 627 4/4
www.sensortechnics.com


▲Up To Search▲   

 
Price & Availability of DDI6000

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X