Part Number Hot Search : 
TPCS8214 D1001 SBL1040C 50VDC X55C2 PLP1000A 4081BD SDP510Q
Product Description
Full Text Search
 

To Download RM4875 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Product Data Sheet
7.5 AMP MODULAR SWITCH MODE RECTIFIER
RM487.5
FEATURES
* SWITCH MODE * >.99 PFC * >84% EFFICIENCY * AUTOMATIC LOAD SHARING * HOT-SWAP CAPABLE * COMPACT SIZE * SHELF MOUNTED * SOFT START TURN-ON!
DESCRIPTION
The RM487.5 Modular Switch-Mode Rectifier is one of C&D Technologies' family of rectifiers that may be used in modular power plants. This unit will function in parallel with any rectifier with similar current sharing capacities. This compact, versatile and efficient unit is ideal for use in advanced telecommunications applications. Its small size allows the user to plan economically for system expansion at minimum cost and makes it ideal for use in fiber optic, microwave and other applications where space is at a premium.
* TELECOM BULK POWER RATED * BELLCORE COMPLIANT * PROCESSOR INTELLIGENCE ALLOWS EXPANSION TO REMOTE CONTROL FEATURES * INFINITE, FULL CURRENT SHORT CIRCUIT CAPABLE * THD <5%
AGENCY APPROVALS PENDING
Internet: http://www.cdpowerelectronics.com Power Electronics Division, United States 3400 E Britannia Drive, Tucson, Arizona 85706 Phone: 800.547.2537 Fax: 520.770.9369 RM4875 4/98 REV A Power Electronics Division, Europe C&D Technologies (Power Electronics) Ltd. 132 Shannon Industrial Estate, Shannon, Co. Clare, Ireland Tel: +353.61.474.133 Fax:+353.61.474.141 Page 1
Input Specifications
Parameter
Operating Range Current
Conditions
45 - 65 Hz, single phase, no taps required 106 VAC 208 VAC 240 VAC
Min
106
Typ
4.6 2.55 2.12 84
Max
264
Units
VAC A A A %
Efficiency Power Factor Correction (PFC)
>.99
MEASUREMENTS OF RM4875
Module Weight Height Depth Width Shelf* Weight Height Depth Width 2.88 lbs. 2.4" 11.0" 4.75" 15.5 lbs. 3.5" with rectifiers mounted in shelf 12" maximum 23" rack mount
* These measurements are specifically for the AGM25 List 1 up to 8 quantity RM 487.5. Please contact factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules These shelf-mounted modules are easy and safe to install or remove while system is operational without affecting the overall system's performance. Parallel Operation and Automatic Load Sharing Forced share connection is made via a hard wire. Sharing is within 10% of the average current for the load applied. Remote Control Enable Signal The rectifier's output voltage control may be changed from internal float and equalize pots to external remote control though a digital ground signal. Current Limit Upon reaching 110% of rated current, the rectifier will automatically limit the current down to short circuit conditions with no fold back. Safety UL/CUL Approved: UL 1950/CSA 950. File Number: E131694 Status Indicator RFA Remote Control Equalize Front Panel Current Test Jacks Normal
Page 2
RM4875 4/98 REV A
Output Specifications
Parameter
Voltage Adjustment Range float voltage equalize voltage 0-100% load within specified input voltage and frequency range within a 10 - 100% rating nominal AC line 48 52 .5 10 >16 <32 <250 56 60 VDC VDC % % mS dBrnc mV p-p
Conditions
Min
Typ
Max
Units
Regulation Load Current Hold-Up Time Filtering Voice band Wide band noise ENVIRONMENTAL Temperature Operating Storage Humidity Altitude Heat Dissipation Audible Noise
@ 20 MHz
non-condensing
-40 -40 -50 -58 0 0 0 264 <55
+65 149 +85 185 95 7000 2133
@54V 5 ft. from any vertical surface
C F C F % ft. m Btu/hr dBa
PROTECTION, ALARM AND CONTROL SYSTEMS
Rectifier Failure Alarm (RFA) Problems occurring because of an unacceptable relationship between the output power and load conditions will cause a Rectifier Failure Alarm (RFA). This alarm consists of a red LED and a flashing green OK LED. Conditions which may lead to an RFA are: Low Current - Output current has decreased to below 5% of its rated value. Unit Shutdown - Any shutdown occurrence due to overvoltage, external shutdown command, unacceptable ambient temperature conditions or low AC input voltage. Load Sharing Terminal Pin Out Of Range - The terminal pin is out of range. Remote Control Terminal Out Of Range - The remote control terminal pins are out of range. Line Sag - This condition occurs when the nominal voltage decreases below 180V. Normal range is 208240V. Fan Malfunction - The fan has stopped operating or is not providing the airflow needed to cool the unit. Over Temperature - The ambient temperature has exceeded 65C. High Voltage Shutdown (HVSD) The unit's built-in high voltage limit is permanently set at 60V. When internal shutdown occurs, the unit may be restarted by a local switch or by a remote signal. Surge Protection The unit will withstand lightning and input surges of 6000V/3000A. Under Voltage Protection When input voltage is below 105 VAC, the rectifier's operation is automatically power limited.
RM4875 4/98 REV A
Page 3
Mechanical
ALL MEASUREMENTS ARE IN INCHES 2.90
I+
EQL FLT REM EQL NORM RFA OFF
2.400
HFM 48-7.5
I-
4.750
10.955
Standard Options are shown, consult factory for other available options.
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes no responsibility for the use of this information, and all use of such information shall be entirely at the user's own risk. Prices and specifications are subject to change without notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D Technologies product for use in life support devices/systems or in aircraft control applications.
Page 4
RM4875 4/98 REV A


▲Up To Search▲   

 
Price & Availability of RM4875

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X